Honeywell DCP200 VCR User Manual


 
DCP200 Profile Controller & Recorder - Product Manual
Page 86 Modbus Parameters 51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Scale Point 13 1078 0x0436 R/W >Scale point 12 to 100.0%
Display Point 13 1079 0x0437 R/W Valid between scale range maximum and minimum
Scale Point 14 1080 0x0438 R/W >Scale point 13 to 100.0%
Display Point 14 1081 0x0439 R/W Valid between scale range maximum and minimum
Scale Point 15 1082 0x043A R/W >Scale point 14 to 100.0%
Display Point 15 1083 0x043B R/W Valid between scale range maximum and minimum
Option Slot A Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Digital Input A Status 2115 0x0845 RO
Value
Digital Input A Status
0 Inactive
1 Active
Option Slot A
Module Type
2116 0x0844 RO
Value
Module Fitted In Slot A
0 None Fitted
1 RS485 Communications
3 Digital Input
4 Auxiliary Input A
5 Ethernet Communications
255
Error (
unrecognised module
)
RS485 Address 2117 0x0845 R/W
Value
RS485 Ad
dress
0 Modbus Master mode
1 to 255 Modbus Slave Address
RS485 Data Rate 2118 0x0846 R/W
Value
Baud Rate
0 4800
1 9600
2
19200 (
Default
)
3 38400
4 57600
5 115200
RS485 Parity 2119 0x0847 R/W
Value
Parity
0 None
1 Even
2 Odd
Auxiliary Input A
Type
2120 0x0848 R/W
Value
Auxiliary A Input Type
0 0 to 20mA DC
1 4 to 20mA DC
2 0 to 10V DC
3 2 to 10V DC
4 0 to 5V DC
5 1 to 5V DC
Target Setpoint
Address
2121 0x0849 R/W Target setpoint parameter address for master mode