Honeywell DCP200 VCR User Manual


 
DCP200 Profile Controller & Recorder - Product Manual
Page 88 Modbus Parameters 51-52-25-150, Issue 1 – April 2009
Paramet
er Name
Modbus Address
Access
Values
(Dec)
(Hex)
Digital Input B Status 2085 0x0825 RO
Value
Digital Input B Status
0 Inactive
1 Active
Calibration Status 2086 0x0826 RO
Value
Calibration Status
0 Calibration OK
1 Calibration Required
Option Slot 1 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Option Slot 1
Module Type
2130 0x0852 RO
Value
Module Fitted In Slot 1
0 None Fitted
1 Single Relay
2 Single SSR Driver
3 Linear mA/V DC
8 Triac
255
Error (
unrecognised module
)
Linear mA/V DC
Output 1 Type
2131 0x0853 R/W
Value
Linear Output 1 Type
0 0 to 5V DC
1 0 to 10V DC
2 2 to 10V DC
3 0 to 20mA DC
4 4 to 20mA DC
5 Variable 0 to 10VDC Transmitter PSU
Digital Output 1
Status
2132 0x0854 RO
Value
Digital Output 1 Status
0 Inactive
1 Active
Linear Output 1
Level Status
2134 0x0856 RO -2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Linear Output 1
Function
2144 0x0860 R/W
Value
Linear Output 1 Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Retransmit Actual Setpoint Value
4 Retransmit Process Variable Value
Digital Output 1
Function
(Relays, SSR
Drivers or Triacs.
Linear Outputs are
mA or VDC)
2146 0x0862 R/W
Value
Digital Output 1 Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Alarm
4 Alarm and Event
Output 1 Alarm
Selection
2148 0x0864 R/W
Valu
e
Output 1 Alarm Selection
0 Alarm 1. Direct Acting