Honeywell DCP200 VCR User Manual


 
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009 Modbus Parameters Page 93
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
20 Event 4 AND Alarm 4. Direct Acting
21 Event 4 AND Alarm 4. Reverse Acting
22 Event 5 AND Alarm 5. Direct Acting
23 Event 5 AND Alarm 5. Reverse Acting
Output 2 Retransmit
Minimum
2182 0x0886 R/W Limited by input range maximum/minimum
Output 2 Retransmit
Maximum
2183 0x0887 R/W Limited by input range maximum/minimum
Option Slot 3 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Option Slot 3
Module Type
2192 0x0890 RO
Value
Module Fitted In Slot 3
0 None Fitted
1 Single Relay
2 Single SSR Driver
3 Linear mA/V DC
8 Triac
9 Dual Relay
10 Dual SSR Driver
11 24VDC Transmitter PSU
255
Error (
unrecognised module
)
Linear mA/V DC
Output 3 Type
2193 0x0891 R/W
Value
Linear Output 3 Type
0 0 to 5V DC
1 0 to 10V DC
2 2 to 10V DC
3 0 to 20mA DC
4 4 to 20mA DC
5 Variable 0 to 10VDC Transmitter PSU
Digital Output 3 or
3A Status
2194 0x0892 RO
Value
Digital Output 3 or 3A Status
0 Inactive
1 Active
Digital Output 3B
Status
2195 0x0893 RO
Value
Digital Out
put 3B Status
0 Inactive
1 Active
Linear Output 3
Level Status
2196 0x0894 RO -2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Linear Output 3 or
3A Function
2203 0x089B R/W
Value
Linear Output 3 or 3A Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Retransmit Actual Setpoint Value
4 Retransmit Process Variable Value