USB Menu
A Notification is shown if a USB Memory Stick is inserted or removed from the USB Port. The
USB Menu will automatically be offered after insertion. The USB menu can also be accessed
from the Main Menu. Refer to the USB Interface section for more details on the use of the
USB port option.
Table 22. USB Menu Screens
USB Menu:
USB Mode Unlocking
Enter correct code number to access USB Menu.
Read/Write To USB
Device?
Select the required action from: Read Instrument Configuration
(from USB stick); Write Instrument Configuration (to USB stick);
Read Profiles (from USB stick); Write Profiles (to USB stick) or Write
Recorder Log File (to USB stick).
Write
Select Profile To
Write
If writing a profile to the USB Memory Stick, choose a profile to write
from the list provided.
Enter A File or
Folder Name
Enter an 8-character folder name for recorder logs, or a file name
for configurations or profiles. An extension (bct for configurations,
.pfl for profiles) is added to files automatically. Caution: Existing
files/folders with the same name will be over-written.
Writing
Profile/Configuration
File
An animated screen is shown while the file(s) are being written.
Caution: Do not disconnect USB device until completed! Data loss
or corruption may result.
Transfer Successful
Confirmation that the data transfer to the USB stick completed
correctly. Press to continue
Transfer Failure
For write failures, check for adequate disk space on the USB stick.
Read
Select File
Select the Configuration or Profile file to transfer from the USB stick.
Caution: A configuration read overwrites all existing instrument
settings.
Reading
Profile/Configuration
File
An animated screen is shown while the file is being read.
Caution: Do not remove the memory stick whist this operation is in
progress. Data corruption may result.
Transfer Successful
Confirmation that the data transfer from the USB stick completed
correctly. Press to continue
Transfer Failure
For read failures, check the maximum number of profiles and/or
segments is not being exceeded.
CAUTION:
Do not remove the memory stick from the USB port whilst a Data Transfer to or from
the USB stick is in progress. Data loss or corruption may result.
CAUTION:
During Data Transfer, normal operation carries on in the background, but operator
access to other screens is not possible. The transfer of a full memory can take up to
7 minutes. Only begin a transfer when you are certain that access (e.g. setpoint
changes) will not be required.