51-52-25-150, Issue 1 – April 2009 Modbus Parameters Page 113
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Event 1 Status 8249 0x2039 RO
Value
Status Of Event 1
0 Event 1 Inactive
1 Event 1 Active
Event 2 Status 8250 0x203A RO
Value
Status Of Event 2
0 Event 2 Inactive
1 Event 2 Active
Event 3 Status 8251 0x203B RO
Value
Status Of Event 3
0 Event 3 Inactive
1 Event 3 Active
Event 4 Status 8252 0x203C RO
Value
Status Of Event
4
0 Event 4 Inactive
1 Event 4 Active
Event 5 Status 8253 0x203D RO
Value
Status Of Event 5
0 Event 5 Inactive
1 Event 5 Active
Segment Type
Status
8258 0x2042 RO
Value
Segment Type Status
0 No segment
1 Setpoint ramping up
2 Step
3 Dwell
4 Held
5 Loop
6 Join
7 End
8 Setpoint ramping down
Currently Active
Profile Name
8259 0x2043 RO The name of the currently selected profile
Secondary Profile
Status
8232 0x2028 RO
Value
0 Profile running
1 Input sensor break
2 Profile not valid
3 Controller in manual mode
4 Profile finished. Profiler is maintaining the
last profile setpoint
5 Profile finished with control outputs off
6 Profile control has ended. Unit is
Controller Mode.
Delay time 8233 0x2029 RO The current start delay time remaining
Current Profile
Running Time
8235 0x202B RO The elapsed time of the current running profile
Current Profile
Remaining Time
8236 0x202C RO The remaining time for the current running profile
Current Segment
Running Time
8237 0x202D RO The elapsed time of the current profile segment