Honeywell DCP200 VCR User Manual


 
DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009 Modbus Parameters Page 97
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Digital Output 4C
Function
2232 0x08B8 R/W
Value
Digital Output 4C Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Alarm
4 Alarm and Event
Digital Output 4D
Function
2233 0x08B9 R/W
Value
Digital Output 4D Function
0 Disabled
1 Primary Output Power
2 Secondary Output Power
3 Alarm
4 Alarm and Event
Output 4A Alarm
Selection
2234 0x08BA R/W
Value
Output 4A Alarm
Selection
0 Alarm 1. Direct Acting
1 Alarm 1. Reverse Acting
2 Alarm 2, Direct Acting
3 Alarm 2. Reverse Acting
4 Alarm 3. Direct Acting
5 Alarm 3. Reverse Acting
6 Alarm 4. Direct Acting
7 Alarm 4. Reverse Acting
8 Alarm 5. Direct Acting
9 Alarm 5. Reverse Acting
10 OR of Alarm 1 or 2. Direct
11 OR of Alarm 1 or 2. Reverse
12 OR of Alarm 1, 2, or 3. Direct
13 OR of Alarm 1, 2, or 3. Reverse
14 OR of Alarm 1, 2, 3, or 4. Direct
15 OR of Alarm 1, 2, 3, or 4. Reverse
16 OR of Alarm 1, 2, 3, 4 or 5. Direct
17 OR of Alarm 1, 2, 3, 4 or 5. Reverse
Output 4B Alarm
Selection
2235 0x08BB R/W
Value
Output 4B Alarm Selection
0 Alarm 1. Direct Acting
1 Alarm 1. Reverse Acting
2 Alarm 2, Direct Acting
3 Alarm 2. Reverse Acting
4 Alarm 3. Direct Acting
5 Alarm 3. Reverse Acting
6 Alarm 4. Direct Acting
7 Alarm 4. Reverse Acting
8 Alarm 5. Direct Acting
9 Alarm 5. Reverse Acting
10 OR of Alarm 1 or 2. Direct
11 OR of Alarm 1 or 2. Reverse
12 OR of Alarm 1, 2, or 3. Direct