Omron C200HW-ZW3AT2-E-V2 Home Theater Server User Manual


 
6SectionTroubleshooting
144
Problem Possible cause Action to be taken
The Controller Link Support Software
is connected to a CV-series PC and
No unit 0202 is displayed.
The CV-series CPU Unit was
manufactured before April 1996.
Set routing tables and set the network
address to the value set in the routing
tables (other than 0).
A data link table is transferred to a
C200HX/HG/HE Controller Link Unit
and Comm err 1104 is displayed.
Word addresses between CI0 236 and
CIO 299 (words that cannot be
specified) are set in the data link table.
Correct the data link table.
The routing tables are transferred to a
C200HX/HG/HE Controller Link Unit
and Cant run 2608 is displayed.
The Routing Table Enabled Bit in the
DM Parameter Area for a
C200HX/HG/HE Controller Link Unit is
set to OFF (disabled).
Turn ON the Routing Table Enabled
Bit in the DM parameter area
(enabled).
Characters are printed abnormally.
The correct printer model is not set. Check whether the printer model in
the System Setup is correct.
The printer settings are incorrect. Check the printer settings.
Printing is not possible from Windows
95.
The property settings of the Controller
Link Support Software are incorrect.
Open the Controller Link Support
Software properties window and
check the Print Screen check box in in
the windows shortcut keys under
Others to see if it is selected.
The Controller Link Support Software
is being operated under Windows 95
and communications errors such as
Wrong network are displayed.
Other applications are running in the
background under Windows 95.
Close other applications running
under Windows 95.
See Appendix D Running Under
Windows 95 for details.