Emerson Process Management Rev AB Projection Television User Manual


 
Option Description
Discrete output Channel B will operate as a discrete output.
6.2 Configure the mA output
The mA output is used to report the configured process variable. The mA output
parameters control how the process variable is reported.
The FVM mA device has two mA outputs: Channel A and Channel B. Both outputs are fully
configurable.
The FVM DO device has one mA output: Channel A. The output is fully configurable.
Important
Whenever you change an mA output parameter, verify all other mA output parameters before
returning the meter to service. In some situations, the transmitter automatically loads a set of stored
values, and these values may not be appropriate for your application.
Configure mA Output Process Variable (Section 6.2.1)
Configure Lower Range Value (LRV) and Upper Range Value (URV) (Section 6.2.2)
Configure Added Damping (Section 6.2.3)
Configure mA Output Fault Action and mA Output Fault Level (Section 6.2.4)
6.2.1 Configure mA Output Process Variable
Display OFF-LINE MAINT > OFF-LINE CONFG > IO > CONFIG MAO 1 > AO 1 SRC
OFF-LINE MAINT > OFF-LINE CONFG > IO > CH B > MAO 2 > CONFIG MAO 2 > AO 2 SRC
ProLink III Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 1 > Source
Device Tools > Configuration > I/O > Outputs > mA Output > mA Output 2 > Source
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > Primary Variable
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > Secondary Variable
Overview
Use mA Output Process Variable to select the variable that is reported over the mA output.
Procedure
Set mA Output Process Variable as desired.
Default settings are shown in the following table.
Integrate the meter with the control system
98 Micro Motion
®
Fork Viscosity Meters (FVM)