Emerson Process Management Rev AB Projection Television User Manual


 
10.19 Check mA Output Fault Action
mA Output Fault Action controls the behavior of the mA output if the transmitter encounters
an internal fault condition. If the mA output is reporting a constant value below 4 mA or
above 20 mA, the transmitter may be in a fault condition.
1. Check the status alerts for active fault conditions.
2. If there are active fault conditions, the transmitter is performing correctly. If you
want to change its behavior, consider the following options:
Change the setting of mA Output Fault Action.
For the relevant status alerts, change the setting of Alert Severity to Ignore.
Restriction
For some status alerts, Alert Severity is not configurable.
3. If there are no active fault conditions, continue troubleshooting.
Related information
Configure mA Output Fault Action and mA Output Fault Level
10.20 Check for radio frequency interference (RFI)
The meter's TPS output or discrete output can be affected by radio frequency interference
(RFI). Possible sources of RFI include a source of radio emissions, or a large transformer,
pump, or motor that can generate a strong electromagnetic field. Several methods to
reduce RFI are available. Use one or more of the following suggestions, as appropriate to
your installation.
Procedure
Use shielded cable between the output and the receiving device.
- Terminate the shielding at the receiving device. If this is impossible, terminate
the shielding at the cable gland or conduit fitting.
- Do not terminate the shielding inside the wiring compartment.
- 360-degree termination of shielding is unnecessary.
Eliminate the RFI source.
Move the meter.
10.21 Check the cutoffs
If the density cutoff is configured incorrectly for your process, any density process
variables and any calculations that rely on density may be based on programmed cutoff
values rather than current density data.
Troubleshooting
Configuration and Use Manual 183