RS-485 connection parameters (continued)Table C-1:
Connection type Parameter Value
Optional or re-
quired? Auto-detection
Baud Rate 1200 to 38400 Optional Yes. The device accepts con-
nection requests that use
any valid setting, and re-
sponds using the same set-
ting.
Parity None, Odd, Even Optional Yes. The device accepts con-
nection requests that use
any valid setting, and re-
sponds using the same set-
ting.
Stop Bits 1 or 2 Optional Yes. The device accepts con-
nection requests that use
any valid setting, and re-
sponds using the same set-
ting.
7. Click Connect.
Need help? If an error message appears:
Switch the leads and try again.
Verify the Modbus address of the transmitter.
Ensure that you have specified the correct port on your PC.
Check the wiring between the PC and the transmitter.
For long-distance communication, or if noise from an external source interferes with the
signal, install 120-½-W terminating resistors in parallel with the output at both ends of
the communication segment.
Ensure that there is no concurrent Modbus communication to the transmitter.
C.2.3 Connect with ProLink III over HART/Bell 202
You can connect directly to the primary mA terminals on the transmitter, to any point in a
local HART loop, or to any point in a HART multidrop network.
CAUTION!
If the transmitter is in a hazardous area, do not remove the transmitter end-cap while the
transmitter is powered up. Removing the end cap while the transmitter is powered up could
cause an explosion. To connect to the transmitter in a hazardous environment, use a
connection method that does not require removing the transmitter end-cap.
Using ProLink III with the transmitter
214 Micro Motion
®