Emerson Process Management Rev AB Projection Television User Manual


 
10.12 Milliamp output problems
Milliamp output problems and recommended actionsTable 10-5:
Problem Possible causes Recommended actions
No mA output Output not powered
Wiring problem
Circuit failure
Verify that the output loop is powered ex-
ternally.
Check the power supply and power supply
wiring. See Section 10.2.
Verify the output wiring.
Check the Fault Action settings. See
Section 10.19.
Contact Micro Motion.
Loop test failed Output not powered
Power supply problem
Wiring problem
Circuit failure
Verify that the output loop is powered ex-
ternally.
Check the power supply and power supply
wiring. See Section 10.2.
Verify the output wiring.
Check the Fault Action settings. See
Section 10.19.
Contact Micro Motion.
mA output below
4 mA
Open in wiring
Bad output circuit
Process condition below LRV
LRV and URV are not set correctly
Fault condition if Fault Action is set to Internal
Zero or Downscale
Bad mA receiving device
Check your process conditions against the
values reported by the device.
Verify the receiving device, and the wiring
between the transmitter and the receiving
device.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.18.
Check the Fault Action settings. See
Section 10.19.
Constant mA output Incorrect process variable assigned to the
output
Fault condition exists
Non-zero HART address (mA Output 1)
Output is configured for loop test mode
Verify the output variable assignments.
View and resolve any existing alert condi-
tions.
Check the HART address. If the HART ad-
dress is non-zero, you may need to change
the setting of mA Output Action (Loop Current
Mode).
Check to see if a loop test is in process (the
output is fixed).
Check HART burst mode configuration.
See Check HART burst mode.
Troubleshooting
Configuration and Use Manual 177