Burst communications, including trigger mode and event notification, is not available on HART/
RS-485. These features are supported only on HART/Bell 202.
Configure HART burst messages
Configure HART trigger mode
Configure HART event notification
Configure HART burst messages
Display Not available
ProLink III Device Tools > Configuration > Communications > Communications (HART)
Field Communicator Configure > Manual Setup > HART > Burst Mode
Overview
Burst messages contain information on process variables or transmitter status. You can
configure up to three burst messages. Each message can contain different information.
Burst messages also provide the mechanism for trigger mode and event notification.
Procedure
1. Navigate to the burst message you want to configure.
2. Enable the burst message.
3. Set Burst Option to the desired content.
Options for burst message contentsTable 6-9:
HART
command
Label
Description
ProLink III Field Communicator
1 Source (Primary Variable) Primary Variable The transmitter sends the primary variable (PV) in
the configured measurement units in each burst
message (e.g., 14.0 g/sec, 13.5 g/sec, 12.0 g/sec).
2 Primary Variable (Percent
Range/Current)
Pct Range/Current The transmitter sends the PV’s actual mA level and
the PV’s percent of range in each burst message
(e.g., 11.0 mA 25%).
3 Process Variables/Current Process Vars/Current The transmitter sends the PV’s actual milliamp read-
ing and the PV, SV, TV, and QV values in measure-
ment units in each burst message (e.g., 11.8 mA,
50 g/sec, 23 °C, 50 g/sec, 0.0023 g/cm3).
9 Read Device Variables with
Status
Device Variables with Status The transmitter sends up to eight user-specified
process variables in each burst message.
33 Transmitter Variables Field Device Vars The transmitter sends four user-specified process
variables in each burst message.