Alert num-
ber Alert title Possible cause Recommended actions
A101 mA Output 1 Fixed The HART address is set to a non-
zero value, or the mA output is con-
figured to send a constant value.
Check whether the output is in loop test
mode. If it is, unfix the output.
Exit mA output trim, if applicable.
Check the HART address. If the HART
address is non-zero, you may need to
change the setting of mA Output Action
(Loop Current Mode).
Check whether the output has been set
to a constant value via digital communi-
cation.
A102 Drive Overrange The drive power (current/voltage) is
at its maximum.
Check the drive gain and the pickoff
voltage. See Section 10.23 and
Section 10.24.
Check for foreign material in the proc-
ess gas or fluid, coating, or other proc-
ess problems.
Check for fluid separation by monitor-
ing the density value and comparing
the results against expected density val-
ues.
Ensure that the sensor orientation is ap-
propriate for your application. Settling
from a two-phase or three-phase fluid
can cause this alert.
A104 Calibration in Pro-
gress
A calibration procedure is in proc-
ess.
Allow the procedure to complete.
A105 Two-Phase Flow The line density is outside the user-
defined two-phase flow limits.
Check for two-phase flow. See
Section 10.22.
A106 Burst Mode Enabled HART burst mode is enabled. No action required.
If desired, you can set Alert Severity Level
to Ignore.
A107 Power Reset Occur-
red
The transmitter has been restarted. No action required.
If desired, you can set Alert Severity Level
to Ignore.