Emerson Process Management Rev AB Projection Television User Manual


 
4 Configure process measurement
Topics covered in this chapter:
Verify the calibration factors
Configure line viscosity measurement
Configure line density measurement
Configure temperature measurement
Configure the pressure input
Configure referred viscosity measurement
Set up the API referral application
Set up concentration measurement
Set up flow rate measurement
4.1 Verify the calibration factors
Display Not available
ProLink III Device Tools > Calibration Data
Field Communicator Configure > Manual Setup > Calibration Factors
Overview
The calibration factors are used to adjust measurement for the unique traits of the sensor.
Your device was calibrated at the factory. However, you should verify that the calibration
factors that are configured in your device match the factory values.
Prerequisites
You will need the factory values for the calibration factors. These are provided in two
locations:
The calibration certificate shipped with your meter
The label inside the transmitter's end-cap
Important
If the transmitter is not the original component, do not use the values from the transmitter label.
Procedure
1. View the calibration factors that are stored in the device.
2. Compare them to the factory values.
If the values match, no action is required.
Configure process measurement
Configuration and Use Manual 17