Alert num-
ber Alert title Possible cause Recommended actions
A113 mA Output 2 Satura-
ted
The calculated mA output value is
outside the configured range.
• Check the settings of Upper Range Value
and Lower Range Value. See
Section 10.18.
• Check process conditions. Actual condi-
tions may be outside the normal condi-
tions for which the output is config-
ured.
• Check for foreign material in the proc-
ess gas or fluid, coating, or other proc-
ess problems.
• Verify that the measurement units are
configured correctly for your applica-
tion.
A114 mA Output 2 Fixed The mA output is configured to
send a constant value.
• Check whether the output is in loop test
mode. If it is, unfix the output.
• Exit mA output trim, if applicable.
• Check whether the output has been set
to a constant value via digital communi-
cation.
A115 No External Input or
Polled Data
The connection to an external
measurement device has failed. No
external data is available.
• Verify that the external device is operat-
ing correctly.
• Verify the wiring between the transmit-
ter and the external device.
• Verify the HART polling configuration.
A116 Temperature Over-
range (API Referral)
The measured temperature is out-
side the range of the API table.
• Check your process conditions against
the values reported by the device.
• Verify the configuration of the API refer-
ral application and related parameters.
See Section 10.10.
A117 Density Overrange
(API Referral)
The measured density is outside the
range of the API table.
• Check your process conditions against
the values reported by the device.
• Verify the configuration of the API refer-
ral application and related parameters.
See Section 10.10.
A118 Discrete Output 1
Fixed
The discrete output has been con-
figured to send a constant value.
• Check whether the output is in loop test
mode. If it is, unfix the output.
A120 Curve Fit Failure
(Concentration)
The transmitter was unable to cal-
culate a valid concentration matrix
from the current data.
• Verify the configuration of the concen-
tration measurement application.
A121 Extrapolation Alert
(Concentration)
The line density or line temperature
is outside the range of the concen-
tration matrix plus the configured
extrapolation limit.
• Check your process conditions against
the values reported by the device.
• Verify the configuration of the concen-
tration measurement application.
Troubleshooting
Configuration and Use Manual 171