Emerson Process Management Rev AB Projection Television User Manual


 
Alert num-
ber Alert title Possible cause Recommended actions
A113 mA Output 2 Satura-
ted
The calculated mA output value is
outside the configured range.
Check the settings of Upper Range Value
and Lower Range Value. See
Section 10.18.
Check process conditions. Actual condi-
tions may be outside the normal condi-
tions for which the output is config-
ured.
Check for foreign material in the proc-
ess gas or fluid, coating, or other proc-
ess problems.
Verify that the measurement units are
configured correctly for your applica-
tion.
A114 mA Output 2 Fixed The mA output is configured to
send a constant value.
Check whether the output is in loop test
mode. If it is, unfix the output.
Exit mA output trim, if applicable.
Check whether the output has been set
to a constant value via digital communi-
cation.
A115 No External Input or
Polled Data
The connection to an external
measurement device has failed. No
external data is available.
Verify that the external device is operat-
ing correctly.
Verify the wiring between the transmit-
ter and the external device.
Verify the HART polling configuration.
A116 Temperature Over-
range (API Referral)
The measured temperature is out-
side the range of the API table.
Check your process conditions against
the values reported by the device.
Verify the configuration of the API refer-
ral application and related parameters.
See Section 10.10.
A117 Density Overrange
(API Referral)
The measured density is outside the
range of the API table.
Check your process conditions against
the values reported by the device.
Verify the configuration of the API refer-
ral application and related parameters.
See Section 10.10.
A118 Discrete Output 1
Fixed
The discrete output has been con-
figured to send a constant value.
Check whether the output is in loop test
mode. If it is, unfix the output.
A120 Curve Fit Failure
(Concentration)
The transmitter was unable to cal-
culate a valid concentration matrix
from the current data.
Verify the configuration of the concen-
tration measurement application.
A121 Extrapolation Alert
(Concentration)
The line density or line temperature
is outside the range of the concen-
tration matrix plus the configured
extrapolation limit.
Check your process conditions against
the values reported by the device.
Verify the configuration of the concen-
tration measurement application.
Troubleshooting
Configuration and Use Manual 171