10.9 Temperature measurement problems
Temperature measurement problems and recommended actionsTable 10-4:
Problem Possible causes Recommended actions
Temperature reading
significantly different
from process temper-
ature
RTD failure
Incorrect compensation factors
Line temperature in bypass does not
match temperature in main line
Verify that the temperature compensation
factors match the value on the sensor tag
or calibration sheet.
If Alert A004, A016, or A017 is active, per-
form the actions recommended for that
alert.
Temperature reading
slightly different from
process temperature
Sensor temperature not yet equalized
Sensor leaking heat
If the error is within the temperature speci-
fication for the sensor, there is no prob-
lem. If the temperature measurement is
outside the specification, contact
Micro Motion.
The temperature of the fluid may be
changing rapidly. Allow sufficient time for
the sensor to equalize with the process flu-
id.
Install thermal installation, up to but not
over, the transmitter housing.
The electrical connection between the RTD
and the sensor may be damaged. This may
require replacing the sensor.
Inaccurate tempera-
ture data from exter-
nal device
Wiring problem
Problem with input configuration
Problem with external device
Problem with input configuration
Verify the wiring between the transmitter
and the external device.
Verify that the external device is operating
correctly.
Verify the configuration of the tempera-
ture input.
Ensure that both devices are using the
same measurement unit.
10.10 API referral problems
Problem Possible causes Recommended actions
No referred density
reading
Line pressure, line temperature, or line
density is outside the range of the config-
ured API table
Check process conditions.
Ensure that the API referral application is
configured correctly for your process fluid.
See Section 4.7.