Viscosity Damping controls the rate of change in the value of the process variable in
transmitter memory. Added Damping controls the rate of change reported via the mA
output.
If mA Output Process Variable is set to Dynamic Viscosity or Kinematic Viscosity, and both Viscosity
Damping and Added Damping are set to non-zero values, viscosity damping is applied first,
and the added damping calculation is applied to the result of the first calculation. This
value is reported over the mA output.
Related information
Interaction between mA Output Damping and process variable damping
4.3 Configure line density measurement
Configure Density Measurement Unit (Section 4.3.1)
Configure Density Damping (Section 4.3.2)
Configure Density Cutoff (Section 4.3.3)
Configure two‐phase flow parameters (Section 4.3.4)
4.3.1 Configure Density Measurement Unit
Display OFF-LINE MAINT > OFF-LINE CONFG > UNITS > DENS
ProLink III Device Tools > Configuration > Process Measurement > Line Density > Density Unit
Field Communicator Configure > Manual Setup > Measurements > Density > Density Unit
Overview
Density Measurement Unit controls the measurement units that will be used in density
calculations and reporting.
Restriction
If the API referral application is enabled, you cannot change the density measurement unit here. The
density measurement unit is controlled by the API table selection.
Procedure
Set Density Measurement Unit to the option you want to use.
The default setting for Density Measurement Unit is g/cm3 (grams per cubic centimeter).
Related information
Set up the API referral application
Configure process measurement
Configuration and Use Manual 21