Emerson Process Management Rev AB Projection Television User Manual


 
Milliamp output problems and recommended actions (continued)Table 10-5:
Problem Possible causes Recommended actions
mA output below
3.6 mA or above
21.0 ma
Incorrect process variable or units assigned
to output
Fault condition if Fault Action is set to Upscale
or Downscale
LRV and URV are not set correctly
Verify the output variable assignments.
Verify the measurement units configured
for the output.
Check the Fault Action settings. See
Section 10.19.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.18.
Check the mA output trim. See
Section 10.16.
Consistently incorrect
mA measurement
Loop problem
Output not trimmed correctly
Incorrect measurement unit configured for
process variable
Incorrect process variable configured
LRV and URV are not set correctly
Check the mA output trim. See
Section 10.16.
Verify that the measurement units are con-
figured correctly for your application.
Verify the process variable assigned to the
mA output.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.18.
mA output correct at
lower current, but in-
correct at higher cur-
rent
mA loop resistance may be set too high Verify that the mA output load resistance
is below the maximum supported load
(see the installation manual for your trans-
mitter).
10.13 Discrete output problems
Problem Possible causes Recommended actions
No discrete output Output not powered
Wiring problem
Circuit failure
Verify that the output loop is powered ex-
ternally.
Check the power supply and power supply
wiring. See Section 10.2.
Verify the output wiring.
Contact Micro Motion.
Loop test failed Output not powered
Power supply problem
Wiring problem
Circuit failure
Circuit failure
Verify that the output loop is powered ex-
ternally.
Check the power supply and power supply
wiring. See Section 10.2.
Verify the output wiring.
Contact Micro Motion.
Discrete output read-
ings reversed
Wiring problem
Configuration does not match wiring
Verify the output wiring.
Ensure that Discrete Output Polarity is set cor-
rectly.
Troubleshooting
178 Micro Motion
®
Fork Viscosity Meters (FVM)