A&D PD4000243 Universal Remote User Manual


 
AD-4402 Page 119
Category address
:
[Function] - [Function setting] - [Sequence] - [Safety]
Category
address
symbol
Name Descriptions
Range
and
choices
Default
5q f-71 to 5q f-75
The maximum eight inputs for safty check are assigned to the
I/O or OP-05. If an input be inactive, the sequence is stopped
and displays sequence error. Refet to 7.5.11. Error Message
and Alarm. These safety checks can use during the
sequence.
Bits map
Bit 1: Safety input 1
Bit 2: Safety input 2
Bit 3: Safety input 3
Bit 4: Safety input 4
Bit 5: Safety input 5
Bit 6: Safety input 6
Bit 7: Safety input 7
Bit 8: Safety input 8
0: No (Not used)
1: Yes (Use)
5q f-71
Batching safety
check
If the assigned input is inactive during
the weighing sequence, it occurs an
sequence error.
5q f-72
Discharge safety
check
If the assigned input is inactive during
the discharge sequence, it occurs an
sequence error.
5q f-73
Recipe safety
check
If the assigned input is inactive during
the recipe sequence, it occurs an
sequence error.
5q f-74
Mixing safety check
If the assigned input is inactive during
the mixture sequence, it occurs an
sequence error.
5q f-75
General safety
check
If the assigned input is inactive during
the all sequence, it occurs an sequence
error.
0000000
0
to
1111111
1
00000
000