Mitsubishi Electronics MELSEC-F Universal Remote User Manual


 
5 - 28
MELSEC-F
COMMUNICATION PROCEDURE5
5 - 28
1) After communicating the parameter settings, confirm the normal
completion of the Ethernet module initial processing.
(Initial completion signal BFM#27 "0001
H")
2) Confirm that the Ethernet module and hub are connected. (BFM#28
b7:ON)
3) Start the open processing writing with pulse execution instruction 0001
H
to BFM#1602.
4) The Ethernet module executes the open processing.
Sends the open request (SYN).
5) When the open processing completes normally
Data communication is enabled.
When the open processing completes abnormally
(*1)
The open error code is stored in the buffer memory.
(*2)
Open error detection (BFM#1602 "0010H" or "0015H")
Area for module status (BFM#28 b6:ON)
6) Start the close processing writing 8000
H to BFM#1602.
7) The Ethernet module executes the close processing.
Sends the close request (FIN).
8) When the close processing completes normally
(*3)
Open completion signal BFM#20480 b0 : ON
BFM#1602 "0005
H"
Open completion signal (BFM#2048 b0) : OFF
Open/Close instruction status (BFM#1602 "0000
H ")
Open status
Open allowed status
Closed status
Initial normal completion
BFM#27=0001
H
OPEN/ CLOSE instruction
status BFM#1602
Open completion signal
BFM#20480
Power-on
1) Parameter update
completed
2)
3)
4) 5) 7) 8)
FINSYN
SYN+ACK
Open request signal
CLOSE
status
0000
H
OPEN
processing
0003
H
CLOSE
processing
0009
H
CLOSE
status
0000
H
FIN+ACK
Hub connected signal
BFM #28b7
BFM#20482
OPEN
instruction
W0001
H
OPEN status
0005
H
(OPEN failure
0010
H)
CLOSE
instruction
W8000
H
Hub connected
6)