Error code
(abnormal
code)
Description of error Error handling
Storage destination
Initial
Open
Fixed
sending
Connection
Error code
E-mail log
BFM#
105
BFM#
124
BFM#
125
BFM#
126
BFM#
229
BFM#
22649
C05F
H
The request could not be executed on the target
PLC.
Correct the network number and PC number.
Correct the content of the read/write request.
C060
H
The content of a request is incorrect.
(Incorrect data was designated for bit devices,
etc.)
Correct the content of the request and send
to the Ethernet module again.
(Correction of data, etc.)
C072
H
The content of a request is incorrect.
(Requested read/write in bit units to word
devices.)
Check whether the content can be requested
to the target PLC.
Correct the content of the request and send it
to the Ethernet module again.
C073
H
Request was not supported by the Ethernet
module of the target PLC.
Review the content of the request.
C086
H
A message exceeding the receive message
size was received.
Correct the send message size from the
requesting source.
C091
H
System Error
(Flash ROM write error)
(*1)
C093
H
System Error
( The parameters written to flash ROM are
abnormal)
(*1)
C0B5
H
Data that could not be processed by the PLC/
Ethernet module was designated.
Review the content of the request.
Cancel the current request.
C0B9
H
The open processing of the applicable
connection is has not been completed.
Execute the open processing.
Check the operation of the external device.
C0BA
H
Cannot acknowledge sending request since the
close processing is being executed via the
CLOSE instruction.
Execute the open processing and make a
sending request.
C0BB
H
System error
The OS detected any error.
(*1)
C0BC
H Designated communication line is closed.
Open the communication line.
Review the target connection number.
C0BD
H
Cannot send by acknowledging continuous
requests.
Check whether or not requests are made
continuously without waiting for responses.
C0BE
H
System error
The OS detected any error.
(*1)
C0BF
H
C0C0H
The receiving completion confirmation signal
was turned on when the receiving completion
signal was not on.
Review and correct the program.
C0C1
H The transmission interval of UDP is too short.
Check whether or not sending requests are
repeated.
Make the sending interval longer.
C0C2
H
to
C0C3
H
System error
The OS detected any error.
(*1)
C0C4
H
Re-initialization was started during
communication
Execute re-initialization after closing all
connections.
C0C5
H
A sending request was made to an external
device whose class/network address are
different from those of the local station when
the router relay function is not used.
The setting of the router relay parameter is
incorrect.
Execute the initial processing by setting that
the router relay function should be used.
Set the correct data for the router relay
parameter.
Correct the IP address of the external device
and execute the open processing.
Check that the network address is correct.
When it is changed, execute the initial
processing again.
C0C6
H
System error
The OS detected any error.
(*1)