4 - 13
MELSEC-F
SETTINGS AND PROCEDURES PRIOR TO OPERATION4
4 - 13
(5) IP Address settings - IP address (BFM #0 to 1)
(a) Set the IP address of the local station according to the specified input format
(decimal or hexadecimal).
It should be set so that the local station Ethernet module and the
communicating external device have the same class and sub-net address
(two words).
(b) It is necessary to use the router relay function in order to communicate with
an external device on another Ethernet network (different sub-net address).
For more details, see Section 5.3, "Router Relay Parameter".
(c) Set the IP address after consulting a network administrator (the person who
plans the network and manages IP addresses).
[IP address]
Values bits 7 to 0
Values bits 31 to 24
to
BFM #1 BFM #0
U \G0
DMOV H0C0A801FE
(Example) Program for "192.168.1.254 (C0 A8 01 FE
H
)"
corresponds to the module number.
U \G25
MOV H9872
IP address "192.168.1.254
(C0 A8 01 FE
H
)" is stored
in BFM #0, #1
Write command for configuration
data to a flash ROM.