Mitsubishi Electronics MELSEC-F Universal Remote User Manual


 
2 - 3
MELSEC-F
SYSTEM CONFIGURATIONS2
2 - 3
(2) Connection using the 10BASE-T
Use devices that satisfy the standards of IEEE802.3 and 10BASE-T.
Shielded twisted pair cable (STP cable), category 3 (4, 5)
* Use a straight cable for connection between a hub and the Ethernet module.
(When connecting an external device to the Ethernet module directly without
a hub use a cross cable.
However, operation is not guaranteed when connecting the Ethernet
module directly to an external device with a cross cable, except when
connecting two Ethernet modules.)
RJ45 plug
10Mbps hub
POINT
During the high-speed communication (100 M bps) via 100BASE-TX
connection, a communication error may occur due to the effect of high
frequency noise from devices other than PLC in a given installation
environment.The following describes countermeasures on the Ethernet module
side to prevent the effect of high frequency noise for construction of a network
system.
(1) Wiring connection
Do not bundle the twisted pair cables with the main circuit and power wires,
and do not install them close to each other.
They should be installed at least 100 mm (3.94 in) away from each other.
Make sure to place the twisted pair cables in a duct.
(2) Communication method
Data communication with an external device is performed using TCP/IP
communication.
Increase the number of communication retries as necessary.
[When the error cannot be solved]
Communication is performed at a data transmission rate of 10 M bps by
changing the connection hub for the Ethernet module to a hub capable of
handling 10 M bps.
External device
Twisted pair cable
Hub
* Up to 4 levels are allowed
for cascade connection
Ethernet module