Mitsubishi Electronics MELSEC-F Universal Remote User Manual


 
5 - 13
MELSEC-F
COMMUNICATION PROCEDURE5
5 - 13
5.3 Router Relay Parameter
This section explains the router relay parameter.
NOTE
When making settings with the FX Configurator-EN, select [Router Relay
Parameters] from the initial screen and adjust the settings at the [Ethernet Router
Relay Parameter Settings] screen.
(1) Router relay function (BFM#2 b4,b5)
(a) Set whether the router relay function will be used or not.
The router relay function is not needed when communicating with the target
device on the same Ethernet network (the subnet address of the IP address
is the same).
(b) The router relay function allows communication with devices on other
Ethernet networks via routers and gateways.
(The router relay function does not mean a function to act as a router.)
(c) One router can be set for the router relay function.
Setting item name BFM number [Decimal] Description of setting Setting range/options
Router relay function
2
(b4, b5)
Select whether the router relay function is not used or is used.
00 : Use
01 : Not used
Sub-net mask pattern 512, 513 Set the sub-net mask. C0000000 to FFFFFFFC
H
Router IP address 514, 515 Set the IP address of the router to be routed through. Other than 00000000H and FFFFFFFFH