5.5 Open Settings
This section explains the open setting.
A sequence program can perform open processing (establishing connection) with up
to a maximum of 8 external device stations
Once a connection is established with an external device, it is possible to
communicate using MC protocol, fixed buffer communication.
Thus, the open processing is required even when communicating using MC protocol.
NOTE
When adjusting settings in FX Configurator-EN, select the [Open Settings] from the
initial screen and adjust the settings at the [Ethernet Open Settings] screen.
*1 Set "A002
H" to the corresponding connection of BFM#32 to #39 for MELSOFT connection.
*2 Refer to (4) in p. 5-20.
(1) Protocol
(connection numbers 1 to 8; BFM#32 to 39 b8)
(a) Select the protocol for each connection.
(b) For protocols (TCP/UDP), see 1.3, "Software Configuration".
Setting item name BFM number [Decimal] Description of setting Setting range/options
Protocol
32 to 39
(b8)
Set the communication method (protocol).
OFF : TCP/IP
ON : UDP/IP
Open system
32 to 39
(b15, b14)
Select the connection open system.
00 : Active open
10 : Unpassive open
11 : Fullpassive open
A002 : MELSOFT connection
*1
Fixed buffer
32 to 39
(b0)
Select the usage of the fixed buffer.
OFF : Send
ON : Receive
Fixed buffer
communication
32 to 39
(b10, b9)
Select which protocol is used for fixed buffer communication.
00 : Procedure exist
10 : MC (App)
*2
01 : No procedure
Pairing open
32 to 39
(b7)
Select whether pairing open is used or not.
OFF : Pairs
ON : No pairs
Existence confirmation
32 to 39
(b1)
Select whether the continued existence of a destination station
for a connection should be confirmed or not.
OFF : No confirm
ON : Confirm
Local station Port No.
40, 47, 54, 61, 68, 75, 82,
89
Set the local station's port No. 1025 to 5548 or 5552 to 65534
Destination IP address
41 to 42, 48 to 49, 55 to
56, 62 to 63, 69 to 70, 76
to 77, 83 to 84, 90 to 91
Set the IP address of an external device. 1 to FFFFFFFE
H
Destination Port No.
43, 50, 57, 64, 71, 78, 85,
92
Set the port No. of an external device. 1025 to 65534
Name of setting Description of setting
TCP Communicate using TCP/IP.
UDP Communicate using UDP/IP.