Mitsubishi Electronics MELSEC-F Universal Remote User Manual


 
11 - 23
MELSEC-F
TROUBLESHOOTING11
11 - 23
Error code
(abnormal
code)
Description of error Error handling
Storage destination
Initial
Open
Fixed
sending
Connection
Error code
E-mail log
BFM#
105
BFM#
124
BFM#
125
BFM#
126
BFM#
229
BFM#
22649
C020
H Data length exceeds the allowable range.
Correct the data length.
If the data transmitted is larger than the
allowable size, divide and then send it.
C021
H
An abnormal end response was received after a
transmission using fixed buffers.
Read the end code of the response from the
connection end code/error log area, and
handle as needed.
C022
H
A response could not be received within the
response monitoring timer value.
The applicable connection was closed while
waiting for a response.
Check the operation of the external device.
Review and correct the response monitoring
timer value.
Check the open status of the applicable
connection.
C023
H
The open processing for the applicable
connection is not completed.
The applicable connection is closed.
Execute the open processing of the
applicable connection.
C030
H A sending error occurred.
Check the operation of the external device.
Send after an arbitrarily selected time has
elapsed because packets may be congested
on the line.
Check that the connection cable is not
dislocated.
C032
H
A TCP ULP timeout error occurred in the TCP/
IP communication.
(An external device does not return ACK.)
Check the operation of the external device.
Correct the TCP ULP timeout value and
execute the initial processing again.
Send after an arbitrarily selected time has
elapsed because packets may be congested
on the line.
Check that the connection cable is not
dislocated.
C033
H
An external device side with the set IP address
does not exist.
Review and correct the external device's IP
address and the Ethernet address.
If the external device has the ARP function,
set the initial value. If not, set the Ethernet
address of the external device.
Check the operation of the external device.
Send after an arbitrarily selected time has
elapsed because packets may be congested
on the line.
Check that the connection cable is not
dislocated.
Just after powering ON, there are cases
when the connected hub is not booted, so
send will occur after an arbitrary time period
has elapsed.
C035
H
The existence of an external device could not
be confirmed within the response monitoring
timer value.
Check the operation of the external device.
Review and correct each setting value for the
existence confirmation.
Check that the connection cable is not
dislocated.
C040
H
Not all the data could be received within the
response monitoring timer value.
Sufficient data for the data length could not
be received.
The remaining part of a message divided at
the TCP/IP level could not be received within
the response monitoring timer value.
Review and correct the data length of the
communication data.
Review and correct each setting value at the
initial processing because the packets may
be congested on the line.
Send the same data from the external device
again.