5 - 17 5 - 17
MELSEC-Q
5 PARAMETER SETTINGS
6) Transient setting
2
Set the execution conditions for the transient transmission.
"Maximum No. of transients in 1 scan"
Set the number of transients (total for one entire network) that a single
network can execute in one link scan.
Valid setting count
: 1 to 255 times
• Default
:2 times
"Maximum No. of transients in one station"
Set the number of transients that a single station can execute in one
link scan.
Valid setting count
: 1 to 10 times
• Default
:2 times
2: When making the transient setting, use the following network module
and GX Developer:
• Remote master and remote I/O stations: First 5 digits of serial No. is
"07102" or later.
• GX Developer: GX Developer Version 8.29F or later