Mitsubishi Electronics QJ7LP25G Universal Remote User Manual


 
2 - 17 2 - 17
MELSEC-Q
2 SYSTEM CONFIGURATION
(4) Applicable modules
The Q series modules can be used on remote I/O stations.
Note that some modules have restrictions.
(a) Functional restrictions
The use of interrupt pointers and dedicated instructions for intelligent
function modules are not supported.
For the restrictions of functions for each module, refer to the user's manual
for the module used.
(b) No. of mountable modules
Module Name No. of mountable modules
QJ71E71-B5, QJ71E71-B2,
QJ71E71-100, QJ71E71
Up to 4
1
QJ61BT11N, QJ61BT11 Up to 4
Modules other than those listed above Up to 64
1: The module with function version B or later is available.
(5) Units/modules not applicable
The following units/modules cannot be used on remote I/O stations.
Item Module model name
Redundant type extension base unit Q65WRB
AnS series extension base unit QA1S65B, QA1S68B, QA65B, QA68B
CC-Link IE Controller Network module QJ71GP21-SX, QJ71GP21S-SX
CC-Link IE Field Network master/local
module
QJ71GF11-T2
MELSECNET/H module
QJ71LP21, QJ71LP21-25, QJ71LP21S-25,
QJ71LP21G, QJ71BR11, QJ71NT11B
Web server module QJ71WS96
MES interface module QJ71MES96
AS-i master module QJ71AS92
High speed data logger module QD81DL96
High speed data communication
module
QJ71DC96
Interrupt module
QI60, QX40H
1, QX70H 1, QX80H 1, QX90H
1
1: These modules cannot be used when switched to interrupt modules by
turning off the function selecting switch (SW2).
(6) ERR. contact of the power supply module
The operation of the ERR. contact of the power supply module differs depending
on the combination with the base unit used. For the operation of the ERR.
contact, refer to the QCPU User's Manual (Hardware Design, Maintenance and
Inspection).