Mitsubishi Electronics QJ7LP25G Universal Remote User Manual


 
7 - 4 7 - 4
MELSEC-Q
7 APPLICATION FUNCTIONS
2) Z(P).REMTO
(Network No. designation)
Z.REMTO
Z: Executed when on
Write command
ZP.REMTO
ZP: Executed when rising
Write command
"Jn"
n3 D1n4 n5 D2
"Jn"
n1 n2
n3 D1n4 n5 D2n1 n2
: If the originating station is a Universal model QCPU, " "(double quotation) for the
first argument can be omitted.
Description of setting Setting range
Jn Target network No. 1 to 239
(n1) Channel number
1 to 8
Word device
2
(n2) Target number
1 to 64
Word device
2
(n3)
Start address input/output number for target intelligent function module
The upper 3 digits of the 4-digit expression designates the start address input/output
number for the intelligent function module mounted to the remote I/O station that is to be
the target.
0 to FE
H
Word device
2
(n4)
Write buffer memory start address
Designates the start address of the buffer memory for the write destination intelligent
function module.
Constant (K, H)
Word device
2
(D1)
Write data storage start address device (Host)
Designates the host start address device for storing the written data.
Word device
2
(n5) Number of write data points (word modules)
1 to 960
Word device
2
(D2)
Write completion device (Host)
Designates the host device to be set to 1 scan on by the write completion.
(D2) · · · · · · OFF: Not completed ON: Completed
(D2) + 1 · · · OFF: Normal ON: Abnormal
Bit device
1
Word device bit designation
3
1: Bit device ........................................... X, Y, M, L, F, V, B
2: Word device ...................................... T, C, D, W, ST, R, ZR
3: Word device bit designation ............. Word device.bit number