1-26 10. DIP Switch Setting
10. DIP Switch Setting
DIP Switch (DIPSW) Setting
Set the terminating resistance for RS-422/485 connection with the DIP switch. When
setting the DIP switch, turn the power off.
- For V708/V708i: - For V710/V710i/V712/V712i:
* Set DIPSW2 to 5 (not used) to the OFF position.
Terminating Resistance Setting (DIPSW6, 7, 8)
• When connecting the PLC at CN1 via RS-422/485 interface, set DIPSW7 to the ON
position.
• For the following connections at modular jack 1 (2), set DIPSW 6 (DIPSW8) to the ON
position.
- Master station for multi-link 2 connection
- Temperature controller network/PLC2Way connection via RS-485
- Connection with the card recorder CREC (optional)
- Connection with the serial extension I/O V-I/O (optional)
- Connection to the V7 unit at the termination of V-link connection via RS-485
100-240VAC
L N
LAN
CN1
MJ1 MJ2
PRINTER
CF
CN5
MEMORY
CN6
Side View Rear View
DIP switch
ON
12345678
CF auto load
MJ2 (modular jack 2) terminating resistance
CN1 RD terminating resistance at pins 24 and 25
MJ1 (modular jack 1) terminating resistance
Not used