9. ACTUAL OPERATION
9.1.1 Zero Adjustment Using Display Unit Switches
This section describes the procedure for zero adjustment using the display unit switches.
(For more details regarding setting methods using these switches, refer to Chapter 5: Basic
Operating Procedures.)
The parameters for zero adjustment are B50/M10: Auto Zero Exe (and either of these
can be used to carry out this procedure). For more details regarding these parameters, refer
to Chapter 6: Parameter Description.
The parameter M10: Auto Zero Exe will be used in the following description.
Once in Setting Mode, use the switch to
move the cursor to M: Ajustment.
Touch the switch to access Sub-item
Parameter Search Mode.
Upon selection of M: Ajustment, the cursor will be
positioned at M10: Auto Zero Exe. (Sub-item
sellection (D))
Touch the switch to access Parameter
Replecement Mode.
Touch the switch to move the cursor to
“Execution”.
Touch the switch to select “Execution”.
In order to request confirmation, the entire display
flashes on and off. Touch the switch once
again at this time to fix selection of the automatic
zero adjustment function.
Auto zero adjustment function is being executed
(about 30 seconds).
When zero adjustment function has been completed,
the system returns automatically to the sub-item
selection screen (D).
F0901.EPS
Setting Mode
Major item
parameter
Setting Mode
K:Diagnosis
M:Adjustment
N:Test
M10:Auto Zero Exe
No Execution
No Execution
Execution
M10:Auto Zero Exe
No Execution
Execution
No Execution
Major item
Sub- item
selection (D)
Major item
Sub- item
selection (D)
M:Adjustment
10:Auto Zero Exe
11:Magflow Zero
M:Adjustment
10:Auto Zero Exe
11:Magflow Zero
M10:Auto Zero Exe
Execution
Sub-item
Parameter
Search Mode
Parameter
Replacement
(execute) Mode
Sub-item
Parameter
Search Mode
Start:
Major Item
Parameter
Search Mode
Now Auto Zero
Executing...