APC AXFA11G TV Converter Box User Manual


 
IM 01E20C01-01E
8-16
8. OPERATION VIA HART COMMUNICATOR
HART Communicator
Polling
Never Poll
Never Poll
Ask Before Polling
Always Poll
Digital Poll
HELP SAVE ESC ENTER
6
Select “Digital Poll” and press ENTER (F4).
F4
(ENTER)
×3
5. HART Output Online Menu Main Menu 4. Utility 1. Configure Communication
1. Polling
AXFA11 : FI-1201
HART Output
1 Poll addr 1
2 Num req preams 5
3 Burst mode On
4 Burst option PV
HELP SAVE HOME ENTER
1
2
Return to the “Online” menu with HOME (F3).
Return to the “Main” menu with a “previous” key.
Select “Utility”.
Select “Configure Communication”.
Select “Polling”.
F3
(HOME)
Open the “Auto Poll” display:
AXFA11 : FI-1201
Online
1 Device Setup
2 PV 20m3/h
3 PV AO1 20mA
4 PV Span 20m3/h
HELP SAVE HOME ENTER
3
JLK
4
HART Communicator
1 Offline
2 Online
3 Frequency Device
4 Utility
HELP SEND HOME ENTER
4
HART Communicator
Utility
1 Configure Communic
2 System Information
3 Listen for PC
4 Storage Location
5 Simulation
HELP SEND HOME ENTER
5
HART Communicator
Configure Communica
1 Polling
2 Contrast
3 Off Time
4 Ignore diagnostics
5 Delete Configs
HELP SEND HOME ENTER
F0819.EPS
F3 : HOME
STU
1
or
STU
1
or
NOTE
1. If “Never Poll” is selected in “Polling” when the address is assigned, the
“Online Menu” cannot be called up and displayed. Be sure to select “Digital
Poll” in “Polling” after assigned the polling address.
2. When the same polling address is assigned for two or more field devices in
multidrop mode, communication with these field devices is disabled.