8-8
8. OPERATION VIA HART COMMUNICATOR
8.3.4.3 Example of Setting Alphanumeric-Type Data: Tag Number
This example describes the setting of the tag number for the alphanumeric-type parameter
Tag’ from “FI-1101” to “FI-1201”.
1
Display Operation
2
Select “Tag”.
The display for the Tag setting appears.
(The default value of “Tag” is blank.)
Move the cursor to “1”.
Then press “2” to change the Tag No. “FI-1101” to “FI-1201”.
3
STU
1
AXFA11 : FI-1101
Basic Setup
1 Tag FI-1101
2 PV Damping
3 MF Set
4 Select Flow Tube
5 Nominal Size Unit
HELP SAVE HOME ENTER
4
AXFA11 : FI-1101
Tag
FI-1101
FI-1100
HELP DEL ESC ENTER
5
F0810.EPS
HELP DEL ESC ENTER
F4
AXFA11 : FI-1101
Basic Setup
1 Tag FI-1201
2 PV Damping
3 MF Set
4 Select Flow Tube
5 Nominal Size Unit
HELP SEND HOME ENTER
Press ENTER (F4) .
Press SEND (F2) to set the data into the AXFA11.
Press HOME (F3), and return to the “Online” menu.
AXFA11 : FI-1201
Basic Setup
1 Tag FI-1201
2 PV Damping
3 MF Set
4 Select Flow Tube
5 Nominal Size Unit
HELP SAVE HOME ENTER
(ENTER)
F2
(SEND)
×4
or
AXFA11 : FI-1101
Tag
FI-1101
FI-1201
1. Device Setup 4. Detailed Setup 1. Basic Setup 1. Tag
NOTE
In case of HART protocol, up to 8 characters can be set with “Tag”.