5. BASIC OPERATING PROCEDURES
5.
BASIC OPERATING PROCEDURES
(USING THE DISPLAY UNIT)
The modification of data settings from the display unit can be carried out using the three
setting switches (infrared switches) - namely, the
, , and switches.
This chapter will provide a description of basic data configuration and the methods to be
used with the three setting switches. The AXFA11 can also be operated using a handheld
Brain Terminal (BT200) or a HART Communicator. (Please refer to Chapter 7 for opera-
tion via Brain Terminal and Chapter 8 for operation via HART Communicator.)
IMPORTANT
Operate the display unit under the condition where direct sunlight, etc.... do not
shine to the setting switches directly when the parameter setting operation is
carried out.
Be sure to set parameters as “Protect” on the write protect function after the finish
of parameter setting. Refer to the “Menu P: Parameter Protection Items” and
section “10.2.2” in detail.
NOTE
(1) Always use the setting switches with the cover of the AXFA11 closed.
(2) Use these switches with them covered by the glass window.
(3) If dirt, dust or other substances surfaces on the display panel glass, wipe
them clean with a soft dry cloth.
(4) The operation with dirty gloves may cause a switch response error.
5.1 Operating Panel Configuration and Functions
(1) Data display area
1st line (Display Select1), 2nd line (Display Select2),
and 3rd line (Display Select3) can be displayed using
parameter settings. The content corresponding to
selected item is shown with the reversed-character on
the right of the line.
(2) Setting switch operations
: Move the layer down, select, and confirm
+ : Move the layer up
(Press the switch while
holding down the switch)
: Move the cursor down (for selection-type
parameters) or increase values (for numeric-
type parameters)
: Move the cursor to the right (for numeric-
type parameters)
+ : Move the cursor up (for selection-
type parameters)
F0501.EPS
(4) Reversed character display
(3) Display items
(2) Setting switches
(1) Data display area
(Infrared switches)