8. OPERATION VIA HART COMMUNICATOR
F4
(ENTER)
AXFA11 : FI-1201
Enter meter value
20.000
HELP DEL ABORT ENTER
8
9
AXFA11 : FI-1201
Fld dev output 20.000
mA equal to reference
meter?
1 Yes
2 No
HELP DEL ABORT ENTER
F4
(ENTER)
F4
(OK)
F3
(HOME)
AXFA11 : FI-1201
NOTE-Loop may be
returned to automatic
control
DEL DEL ABORT OK
10
11
AXFA11 : FI-1201
Adjustment
1 Auto Zero Exe
2 Magflow Zero
3 D/A trim
4 Scaled D/A trim
HELP SAVE HOME OK
F0814-3.EPS
Ammeter reading: 19.050
Carry out the same procedures as those described in .
Ammeter reading: 20.000
Returning fld dev to original output” appears.
Press OK (F4).
Press HOME (F3), and return to the “Online” menu.
5
‘19.050’
F4
(ENTER)
F4
(OK)
AXFA11 : FI-1201
Fld dev output 4.000
mA equal to reference
meter?
1 Yes
2 No
DEL DEL ABORT ENTER
6
7
AXFA11 : FI-1201
Setting fld dev
output to 20mA
HELP DEL ABORT OK
Ammeter reading: 4.000
Because the reading on the ammeter is 4.000 mA, select “Yes
and press ENTER (F4).
If the reading is not 4.000 mA, select “No”.
Repeat step until the ammeter reads 4.000 mA.
Press OK (F4), and the AXFA11 outputs an output signal of
100%.
5