8-10
8. OPERATION VIA HART COMMUNICATOR
8.3.4.5 Example 2 of Other Settings: Power Frequency (For DC version only)
IMPORTANT
In situation where a DC power supply is used for converters, set the local com-
mercial power frequency in area where the converter is lnstalled. The flowmeter is
set to 50.00 Hz at the factory.
Set “No” for “Power Synch” and the local commercial power frequency for
“Power Frequency”.
1. Device Setup 4. Detailed Setup 4. Function Set 5. Aux Power Frequency
AXFA11 : FI-1201
Power Frequency
50.00 Hz
50.00
DEL DEL ESC
ENTER
2
3
Enter “60.00” with alphanumeric keys.
Press ENTER (F4).
Press SEND (F2) to set the data into the AXFA11.
Press HOME (F3), and return to the “Online” menu.
4
Open the “Power freq” setting display:
‘60.0’
AXFA11 : FI-1201
Power Frequency
50.00
60.00
DEL DEL ESC ENTER
F4
(ENTER)
F2
(SEND)
F3
(HOME)
F0813.EPS
AXFA11 : FI-1201
Aux
6 Dead Time Os
7 Pulsing Flow No
8 T/P Damp Select
9 Power Synch No
Power Frequency
HELP SAVE HOME
ENTER
1
AXFA11 : FI-1201
Aux
6 Dead Time Os
7 Pulsing Flow No
8 T/P Damp Select
9 Power Synch No
Power Frequency
HELP SAVE HOME ENTER
Select “Power Frequency”.
×9