6. PARAMETER DESCRIPTION
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
T0604-2.EPS
C60
(SELF CHECK)
See “6.5 Alarm Functions”.Good
Error
R
m/s 3
C44 Velocity Check
(VELOCITY CHK)
Display of the span setting using
flow velocity (m/s).
0.000 to 99.999R
C45 Density Unit
(DENSITY UNIT)
Sets units for density when mass
flow rate is selected.
kg/m
3
lb/gal
lb/cf
W kg/m
3
C45 0 to 4
C46 Mass Flow Density
(MASS DENSITY)
Sets density when mass flow rate
is selected (with units from C45).
0 to 32000W0
C47 User Span Select
(USER SPN SEL)
Selects whether or not special
units are used for flow rate units.
No
Yes
WNo
C48 Flow User Unit
(FL USER UNIT)
Sets the special flow rate units.8 alphanumeric
characters
W
C48
0 to 4
C49 Flow User Span
(FL USER SPAN)
Sets span when using special flow
rate units.
0.0001 to 32000W 100
(4) Item D (Menu D): Total Setting items
Menu D contains setting items such as the totalization scale and the forward/reverse totalized values.
T0605.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
D10 Total Unit
(TOTAL UNIT)
Wn Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s
Pulse/s (*) Selects the flow rate unit per one
pulse as used for totalization
display. Linked with B30.
D12 Total Decimal Pnt
(TL DECIMAL)
W0
1
2
3
4
5
6
7
0 Selects position of decimal point
for totalization display
D11 Total Scale
(TOTAL SCALE)
W0 to 32000 D10
(B30)
0 to 4 0 (*) Sets the flow rate per one pulse
for the totalization display.
Linked with B31.
Sets the range in vicinity of 0%
within which the totalization
display will be halted.
D13 Total Low Cut
(TOTAL LOWCUT)
W0 to 100 % 0 3 %
Sets the totalization preset value
in the lower 6 digits of the 8-digit
totalized value.
D21 Ttl Set Val Lower
(TL SET VAL L)
W0 to 999999 0 0
Sets the totalization preset value
in the upper 2 digits of the 8-digit
totalized value.
D22 Ttl Set Val Upper
(TL SET VAL U)
W0 to 99 0 0
Sets the totalization switch value
in the lower 6 digits of the 8-digit
totalized value.
D23 Ttl Switch Lower
(TL SWITCH LO)
W0 to 999999 0 0
Sets the totalization switch value
in the upper 2 digits of the 8-
digits totalized value.
D24 Ttl Switch Upper
(TL SWITCH UP)
W0 to 99 0 0
Selects whether or not special
units are used as totalized units.
D30 Ttl User Select
(TL USER SEL)
WNo
Yes
No
Sets the special totalized units.
D31 Ttl User Unit
(TL USER UNIT)
W8 alphanumeric
characters
See “6.5 Alarm Functions”.
D60
(SELF CHECK)
RGood
Error
Executes “Start” or “Stop” of the
totalization function, or executes
“Preset Total” or “Preset Rev
Total”.
D20 Total Execution
(TOTAL EXEC)
W Start
Stop
Preset Total
Preset Rev Total
Start
D00 Total Set
(TOTAL SET)