8. OPERATION VIA HART COMMUNICATOR
8.3.4.7 Example 4 of Other Settings: Burst Mode
The AXFA11 continuously sends its stored data when the “Burst mode” is set to “On”.
Any one of instantaneous flow rate, output in %, totalization values or current output can
be selected and sent. The data is sent intermittently as a digital signal when the AXFA11 is
set in the “Burst mode.
Setting of Burst Mode
1. Device Setup 4. Detailed Setup 5. HART Output 4. Burst option
AXFA11 : FI-1100
Burst option
********
PV
% range/current
Process vars/crnt
HELP DEL ESC ENTER
Select the type of data to be sent.
Instantaneous flow rate (PV)
Output in % and current output (% range/current)
Instantaneous flow rate, totalization value* and current
output (Process vars/crnt)
* “Totl”, “Reverse Totl” or “Dif Totl”
Open the “Burst option” display:
5. HART Output 3. Burst mode
AXFA11 : FI-1100
Burst mode
Off
Off
On
DEL DEL ESC
ENTER
1
F4
2
Select “On” and press ENTER (F4).
Press SEND (F2).
(ENTER)
F2
(SEND)
Call up “Burst mode” display.
AXFA11 : FI-1100
HART Output
1 Poll addr 0
2 Num req preams 5
3 Burst mode On
4 Burst option PV
HELP SEND HOME
ENTER
F4
(ENTER)
F2
(SEND)
F0817.EPS
Exiting Burst Mode
Open the “Burst mode” display, and select “Off”.
8.3.4.8 Example 5 of Other Settings: Multidrop Mode
Field devices in “Multidrop Mode” refers to the connection of several field devices on a
single communication line. Up to 15 field devices can be connected when set to the
multidrop mode. To activate multidrop communication, the field device address must be
changed to a number from 1 to 15. This change deactivates the 4 to 20 mA output and
changes it to 4 mA.
Setting of Multidrop Mode
1. Device Setup 4. Detailed Setup 5. HART Output 1. Poll addr
AXFA11 : FI-1100
Poll addr
0
0
HELP DEL ESC ENTER
Set the polling address (a number from 1 to 15) and press
ENTER (F4).
Then, press SEND (F2) to send the data.
Open the “Poll addr” display:
F4
(ENTER)
‘1’
F2
(SEND)
F0818.EPS