6. PARAMETER DESCRIPTION
T0608-2.EPS
Item
Name
Display unit
(BRAIN)
Data range
Display unit
/BRAIN
Default value
(*): Indicated item
Units
R/W
Position
of decimal
point
Description
G14 H/L Alarm Hys
(H/L ALM HYS)
W%00 to 10 5 % Sets hysteresis width for high-low
flow rate limit alarm
G20 Alm Out Act Mode
(
ALM OUT ACT)
W Closed(On) Act
Open(Off) Act
Open(Off)
Act
Selects whether alarm output will
be set to “On Active” or “Off Active.”
G22 4-20mA Burn Out
(4-20 BURNOUT)
R High
Low
Displays the current output
during a CPU failure.
G30 Alm-Setting
(ALM-SETTING)
WNo
Yes
Yes
Selects whether a setting alarm is
to be specified as an alarm.
G31 Alm-Sig Over
(ALM-SIG OVER)
WNo
Yes
Yes
Selects whether a signal overflow
alarm is to be specified as an alarm.
G32 Alm-Emp Pipe
(ALM-EMP PIPE)
WNo
Yes
Yes
Selects whether an empty pipe alarm
is to be specified as an alarm.
G33 Alm-HH/LL
(ALM-HH/LL)
WNo
Yes
No
Selects whether a flow rate
high-high or low-low alarm is
to be specified as an alarm.
G34 Alm-Adhesion
(ALM-ADHESION)
WNo
Yes
No
Selects whether an electrode adhesion
alarm is to be specified as an alarm.
G40 Operation Time
(OPERATE TIME)
R 0D 00:00 to
99999D 23:59
Operation time
G42 Alm Record Time1
(ALM TIME 1)
R 0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the most recent alarm.
G43 Alm Record2
(ALM RECORD2)
RSee G41 Displays the content of the second
most recent alarm.
G44 Alm Record Time2
(ALM TIME 2)
R 0D 00:00 to
99999D 23:59
Displays the operation time at occurrence
of the second most recent alarm.
G45 Alm Record3
(ALM RECORD3)
RSee G41
Displays the content of the third most
recent alarm.
G46 Alm Record Time3
(ALM TIME 3)
R 0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the third most recent alarm.
G47 Alm Record4
(ALM RECORD4)
RSee G41 Displays the content of the fourth
most recent alarm.
G48 Alm Record Time4
(ALM TIME 4)
R 0D 00:00 to
99999D 23:59
Displays the operation time at the
occurrence of the fourth most recent alarm.
G60
(SELF CHECK)
RGood
Error
See “6.5 Alarm Functions”.
G21 4-20mA Alarm Out
(4-20 ALM OUT)
W 2.4mA or Less
4.0mA
Hold
21.6mA or More
21.6mA or
More
Selects the current output during
alarm occurrence.
G41 Alm Record1
(ALM RECORD1)
R
10:uP Fault
11:EEPROM Fault
12:A/D(H) Fault
13:A/D(L) Fault
14:A/D(Z) Fault
15:Coil Open
16:
EEPROM Dflt
18:Power Off
19:Inst Pwr Fail
28:WDT
30:Sig Overflow
31:Empty Pipe
33:Adhesion Alm
Displays the content of the most
recent alarm.