6.7 Outputs Configuration
Overview
This group lets you select the signal that will be transmitted.
Accessing Outputs Menu
• Press
Setup
to display the Main menu.
• Use the
keys to select “Outputs” then press
Enter
to enter the sub-menu.
• Output 1, Output 2, or Output 3 and their associated parameters are available
for selection.
• Press to highlight the desired menu selection then press
Enter
to display the
group of parameters.
Refer to “Section 6.4.1 - General Rules for Editing”.
Table 6-6 Outputs Configuration
Sub-menu
selection
Parameter Selection or Range
of Setting
Parameter Definition
Source
Any Analog Signal
See Table 6-3
Process Variable Source - Selects the signal
that will be transmitted.
See Note 1 for units.
High Range -99999.00 to 99999.00
High Range Value - value of input that
corresponds to 100 % output value.
See Note 1 for units.
Low Range -99999.00 to 99999.00
Low Range Value - value of input that
corresponds to 0 % output value.
See Note 1 for units.
Slew Time 0.000 to 999.00
in seconds
default = 0.000
Slew Time is the maximum rate of change
required to drive the output from full OFF (0% -
typically 4 mA) to full ON (100% - typically
20mA).
mA Range High 0 to 20
default = 20
Value of mA output that corresponds to 100 %
output signal (for example: 20 mA).
mA Range Low 0 to 20
default = 4
Value of mA output that corresponds to 0 %
output signal (for example: 4 mA).
mA Limit High 0 to 21
default = 21
Value of mA that you want to set the High
Range Limit.
Output 1
Output 2
Output 3
mA Limit Low 0 to 21
default = 3
Value of mA that you want to set the Low
Range Limit.