Honeywell UDA2182 TV Converter Box User Manual


 
Configuration
74 UDA2182 Universal Dual Analyzer Product Manual January 2009
6.7 Outputs Configuration
Overview
This group lets you select the signal that will be transmitted.
Accessing Outputs Menu
Press
Setup
to display the Main menu.
Use the
keys to select “Outputs” then press
Enter
to enter the sub-menu.
Output 1, Output 2, or Output 3 and their associated parameters are available
for selection.
Press to highlight the desired menu selection then press
Enter
to display the
group of parameters.
Refer to “Section 6.4.1 - General Rules for Editing”.
Table 6-6 Outputs Configuration
Sub-menu
selection
Parameter Selection or Range
of Setting
Parameter Definition
Source
Any Analog Signal
See Table 6-3
Process Variable Source - Selects the signal
that will be transmitted.
See Note 1 for units.
High Range -99999.00 to 99999.00
High Range Value - value of input that
corresponds to 100 % output value.
See Note 1 for units.
Low Range -99999.00 to 99999.00
Low Range Value - value of input that
corresponds to 0 % output value.
See Note 1 for units.
Slew Time 0.000 to 999.00
in seconds
default = 0.000
Slew Time is the maximum rate of change
required to drive the output from full OFF (0% -
typically 4 mA) to full ON (100% - typically
20mA).
mA Range High 0 to 20
default = 20
Value of mA output that corresponds to 100 %
output signal (for example: 20 mA).
mA Range Low 0 to 20
default = 4
Value of mA output that corresponds to 0 %
output signal (for example: 4 mA).
mA Limit High 0 to 21
default = 21
Value of mA that you want to set the High
Range Limit.
Output 1
Output 2
Output 3
mA Limit Low 0 to 21
default = 3
Value of mA that you want to set the Low
Range Limit.