Configuration
80 UDA2182 Universal Dual Analyzer Product Manual January 2009
Sub-menu
selection
Parameter Selection or Range
of Setting
Parameter Definition
Pulse Output relay will provide a fixed duty cycle when the applied input signal is ON. The
cycle time and pulse duration are configurable parameters. The relay will be OFF when the
applied input is OFF. An inverse parameter allows the input to be inverted for reverse
behavior.
Source
Any Digital Signal
See Table 6-4
PV Source
Invert Enable
Disable (default)
The digital output relays "invert" parameter can
be used to allow direct (invert disabled) or
reverse (invert enabled) control actuation.
Cycle Time 0 to 999
default = 10.0
Cycle time is that time period, in seconds,
between relay activations.
Relay 1
Relay 2
Relay 3
Relay 4
Pulse Output
Control Relay
On Time
0 to 999
default = 5.0
The time in seconds that the relay is On during each
cycle when the input to the Pulse Output is ON. When
the Input to the Pulse output is OFF the relay is not
activated.