Configuration
January 2009 UDA2182 Universal Dual Analyzer Product Manual 85
6.11 Math Configuration
Overview
The Math group has four Math selections (Math 1, Math 2, Math 3, and Math 4). Math
selections can be connected to any Analog Signal source (Table 6-3). Math blocks
include scaling for the linear selection only.
The Math Block can also be used for proportional control over the math blocks
configured range for control of any Input PV, Temperature, or calculated values by
connecting it to a current output, TPO relay, or FPO relay. Since multiple outputs can
share a common math block, the output range of a math block can be split over multiple
outputs or relays with each output or proportional relay using a specific portion of the %
output range of the math block.
Accessing Math Menu
• Press
Setup
to display the Main menu.
• Use the keys to select “Math” then press
Enter
to enter the sub-menu.
• Press to highlight the desired menu selection then press
Enter
to display the
group of parameters.
Refer to “Section 6.4.1 – “General Rules for Editing”.