Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
B-33
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
2. Caution regarding convenient function setting
Even if the data addition function is used, the value before adding the addition data (BFM #61 to #64) will
be checked to detect the over-scale error.
To use the peak value automatic transfer function (b4 of BFM #22), be sure to enable the peak value
holding function (b3 of BFM #22).
To use the upper/lower limit error status data automatic transfer function (b5 of BFM #22), be sure to
enable the upper/lower limit value detection function (b1 of BFM #22).
To use the abrupt change detection status data automatic transfer function (b6 of BFM #22), be sure to
enable the abrupt change detection function (b2 of BFM #22).
3. Caution regarding EEPROM writing
If data is written to BFM #0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.