A-9
2 Description of Analog Products
2.2 List of Analog Product Models
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
2.2 List of Analog Product Models
The analog input/output products compatible with the FX3U/FX3UC/FX3G Series PLC are described below:
2.2.1 Expansion board
•FX3G Series PLC
2.2.2 Special adapter
Type
No. of
channels
Range Resolution Function
Refer-
ence
Voltage/current input
FX3G-2AD-BD 2ch
Voltage: 0V to 10V DC 2.5mV(12bits)
Combined use of voltage and
current inputs is possible.
D
Current: 4mA to 20mA DC 8μA(11bits)
Voltage/current output
FX3G-1DA-BD 1ch
Voltage: 0V to 10V DC 2.5mV(12bits)
Voltage and current output. G
Current: 4mA to 20mA DC 8μA(11bits)
Type
No. of
channels
Range Resolution Function
Refer-
ence
Voltage/current input
FX3U-4AD-ADP 4ch
Voltage: 0V to 10V DC 2.5mV(12bits)
Combined use of voltage and
current inputs is possible.
C
Current: 4mA to 20mA DC 10μA(11bits)
Voltage/current output
FX3U-4DA-ADP 4ch
Voltage: 0V to 10V DC 2.5mV(12bits)
Combined use of voltage and
current outputs is possible.
F
Current: 4mA to 20mA DC 4μA(12bits)
Voltage/current input/output mixture
FX3U-3A-ADP
Input
2ch
Voltage: 0V to 10V DC 2.5mV(12bits)
Combined use of voltage/
current inputs and voltage/
current output is possible.
H
Current: 4mA to 20mA DC 5μA(12bits)
Output
1ch
Voltage: 0V to 10V DC 2.5mV(12bits)
Current: 4mA to 20mA DC 4μA(12bits)
Temperature sensor input
FX
3U
-4AD-PT-ADP
4ch Pt100: -50°C to +250°C0.1°C
Compatible with the platinum
resistance thermometer
sensor (Pt100).
The product can be switched
between "Centigrade" and
"Fahrenheit."
I
FX
3U
-4AD-PTW-ADP
4ch Pt100: -100°C to +600°C0.2°C to 0.3°C
Compatible with the platinum
resistance thermometer
sensor (Pt100).
The product can be switched
between "Centigrade" and
"Fahrenheit."
J
FX
3U
-4AD-PNK-ADP
4ch
Pt1000: -50°C to +250°C
0.1°C
Compatible with the input
sensor (Pt1000 and Ni1000).
The product can be switched
between "Centigrade" and
"Fahrenheit."
K
Ni1000: -45°C to +115°C
FX
3U
-4AD-TC-ADP
4ch
Type K: -100°C to +1000°C0.4°C
Compatible with
thermocouple types K and J.
The product can be switched
between "Centigrade" and
"Fahrenheit."
L