3 Wiring
3.6 Caution Regarding Wiring
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
K
FX
3U
-4AD-PNK
-ADP
L
FX
3U
-4AD-TC
-ADP
M
PID Instruction
(FNC 88)
3.5.2 Wiring of the thermocouple type J
*1. To use a J thermocouple type, be sure to connect the thermocouple to these terminals. In addition,
select J type by turning on the type K/J selection special auxiliary relay.
*2. Keep the thermocouple away from inductive noise (commercial power, etc.).
3.6 Caution Regarding Wiring
It is not possible to connect different types of thermocouples to 4 channels of TC-ADP. Be sure to use the
same type of thermocouple for all the channels.
TC-ADP is not insulated between the channels. For this reason, be sure to use a non-grounded type
thermocouple.
Be sure not to connect to the terminal "".
3.7 Grounding
Grounding should be performed as stated below.
The grounding resistance should be 100Ω or less.
Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
The grounding wire size should be AWG22 to 20 (0.3 to 0.5 mm
2
).
The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
3k
Ω
ch
TC-ADP
Class-D
grounding
+5V
L
+
L
-
24+
24-
Terminal block
24V DC
L
+, L
-, ch
:
represents the channel number.
type J
Thermocouple
type J
*2
ch
L
+
L
-
3k
Ω
Shield
*1
Compensating
lead wire
Temperature
compensating circuit
Temperature
compensating circuit
type J
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition