Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
G-11
3 Wiring
3.2 Applicable Cables and Terminal Tightening Torque
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel analog Output)
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
3.2 Applicable Cables and Terminal Tightening Torque
Use the following cables to connect with the counterpart equipment. Terminate the cable end as shown below.
1. Cable
Applicable cable and tightening torque
2. Termination of cable end
To terminate the cable, treat the stranded/single wire directly or use a rod terminal with insulation sleeve.
To directly terminate the end of a stranded/single-wire cable:
- Twist the end of the stranded cable so that the "barbed wires"
cannot protrude.
- Do not solder-plate the end of the cable.
To terminate cable end using a rod terminal with insulation sleeve:
If the cable cover is too thick, it may be difficult to insert the cable into
the insulation sleeve. For this reason, select an appropriate cable while
referring to the external view.
3. Tool
To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
be able to be achieved. Use the following recommended screwdriver or
an appropriate replacement (grip diameter: approximately 25mm).
Wire size (stranded/
single-wire)
Tightening
torque
Termination
Single-wire
0.3mm
2
to 0.5mm
2
(AWG22 to 20)
0.22N•m to
0.25N•m
To connect a stranded cable, peel the cover off the cable
and then twist the core before connection.
To connect a single-wire cable, just peel the cover off the
cable before connection.
2-wire
0.3mm
2
(AWG22)
Rod terminal
with
insulation
sleeve
0.3mm
2
to 0.5mm
2
(AWG22 to 20)
(Refer to the rod terminal
external view shown in
the following figure.)
Rod terminal with insulation sleeve
(recommended terminal)
AI 0.5-8WH : Manufactured by Phoenix Contact
Caulking tool
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
Manufacturer Model Caulking tool
Phoenix Contact AI 0.5-8WH
CRIMPFOX ZA 3
(or CRIMPFOX UD 6)
Manufacturer Model
Phoenix Contact SZS 0.4×2.5
9mm
Termination of cable end
(0.35")
8mm (0.31")
Contact area
(Crimp area)
14mm
2.6mm
(0.1")
Insulation sleeve
(0.55")
0.4mm 2.5mm
The head
should be
straight.
(0.01")
(0.09")