FX3U-4DA (4-channel Analog Output)
4. Analog Output
This chapter describes the minimum programming necessary for analog output by the FX3U-4DA.
Follow the procedure below to confirm that correct analog values can be output.
4.1 Analog Output Procedures
1 Unit number check
Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
When the units/blocks are connected to the FX
3UC
-32MT-LT(-2) PLC, the unit numbers from 1 to 7
are assigned. Check the unit number assigned to the FX
3U
-4DA.
2 Output mode (BFM #0) setting
Depending on the analog signal generator to be connected, set the output mode (BFM #0) for each
channel.
Use hexadecimal numbers for output mode setting. Set the corresponding channel digit to the
output mode setting value specified in the following table:
For a detailed description of the standard output characteristics, refer to Section 2.4.
For a detailed description of the output mode (BFM #0), refer to Subsection 5.4.1.
Setting
value
Output mode Analog output range Digital input range
0 Voltage output mode -10V to +10V -32000 to +32000
1
Voltage output
analog value mV specification mode
-10V to +10V -10000 to +10000
2 Current output mode 0mA to 20mA 0 to 32000
3 Current output mode 4mA to 20mA 0 to 32000
4
Current output
analog value μA specification mode
0mA to 20mA 0 to 20000
F Channel not used