4 Comparison of Performance Specifications
4.3 Mixed Analog Input/Output
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
2. Analog output
3. Other
Specifications
FX2N-5A
Voltage output Current output
Number of output points 1ch
Analog output range
-10V to +10V DC
(External load: 5k to 1MΩ)
0mA to 20mA DC
4mA to 20mA DC
(External load: 500Ω or less)
Offset -10V to +5V 0mA to 10mA
Gain
-9V to +10V, and
Gain - Offset 1V
3 mA to 30 mA or less, and
Gain - Offset 3mA
Digital input/output With sign, 12 bits, binary 10 bits, binary
Resolution 5mV(10V×1/4000) 20μA(20mA×1/1000)
Overall accuracy
Ambient temperature:
25±5°C
±0.5% (±100mV) for 20V full scale
±0.5%(±200μA) for 40mA full scale
Same accuracy for 4mA to 20mA output
Ambient temperature:
0±55°C
±1.0% (±200mV) for 20V full scale
±1.0%(±400μA) for 40mA full scale
Same accuracy for 4mA to 20mA output
Time required for conversion 2ms
I/O characteristics
Specifications FX2N-5A
Insulation method
The photocoupler is used to insulate the analog input and output area from the
PLC.
The DC/DC converter is used to insulate the power supply from the analog input
and output.
Channels are not insulated from each other.
Number of I/O points
occupied
8 points (Taken from either the input or output points of the PLC.)
z
When the output mode is set to "0":
0
+32000
+10V
-10V
-32000
+32767
-32768
z
When the output mode is "4":
(The dotted line is for mode 2.)
0
32000
20mA
Digital input
4mA
Analog output
32767