Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
E-37
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
A
Common Items
B
FX
3U
-4AD
FX
3UC
-4AD
C
FX
3U
-4AD-ADP
D
FX
3G
-2AD-BD
E
FX
3U
-4DA
F
FX
3U
-4DA-ADP
G
FX
3G
-1DA-BD
H
FX
3U
-3A-ADP
I
FX
3U
-4AD-PT
-ADP
J
FX
3U
-4AD-PTW
-ADP
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
5.4.21 BFM #63: Specification of data register for automatic transfer at disconnection
detection
Setting range: 0 to 7999
Initial value: K202
Numeric data type: Decimal (K)
Use this function to automatically transfer the disconnection detection status data (BFM #28) to the data
register specified in BFM #63.
Only when wire-break is detected, data will be automatically transferred from FX
3U-4DA to the PLC. For this
reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
For a detailed description of the disconnection detection status (BFM #28),
refer to Subsection 5.4.9.
1. If "BFM #63 = K202 (initial value)"
2. Cautions regarding disconnection detection status automatic transfer function setting
If a data is already specified for the other automatic transfer functions, do not specify the same data
register.
This function is valid by turning on b2 of the status automatic transfer function setting (BFM #60).
When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.
The data set in BFM #63 will be retained in the EEPROM.
3. Cautions regarding EEPROM writing
If data is set in BFM #0, #5, #10 to #17, #19, #32 to #35, #50 to #54 or #60 to #63, the data will be written in
the EEPROM of FX
3U-4DA.
Do not turn off the power immediately after writing values in these buffer memories.
The maximum number of EEPROM rewritable times is 10,000. Therefore, when creating a program, do not
frequently write data in the above buffer memories (BFM).
5.4.22 BFM #80 to #3098: Table output function
Related BFM:
BFM #80 (start/stop command of table output function)
BFM #81 to #84 (output pattern setting of channels)
BFM #85 to #88 (output execution cycle number of channels)
BFM #89 (completion flag of table output function)
BFM #90 (table output error code)
BFM #91 (table output error source number)
BFM #98 (data table head device number)
BFM #99 (data table transfer command)
BFM #100 to #398, •••, #2800 to #3098 (data table in patterns)
Table output function: Sets predetermined output patterns as data table, and outputs analog signals
according to the data table.
For a detailed description of the table output function, refer to Chapter 6.
Specified data
register
Description
D202 Value of disconnection detection status (BFM #28)