Mitsubishi Electronics MELSEC-F Home Theater Server User Manual


 
G-12
3 Wiring
3.3 Analog Output Line
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel analog Output)
3.3 Analog Output Line
*1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2. Ground the shielded wire at one point on the signal receiving side.
3.4 Grounding
Grounding should be performed as stated below.
The grounding resistance should be 100Ω or less.
Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
For details, refer to User’s Manual - Hardware Edition of the PLC Series.
The grounding wire size should be AWG22 to 20 (0.3 to 0.5 mm
2
).
The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
I+
VI-
V+
I+
VI-
V+
If voltage output is selected:
If current output is selected:
*1 Shield
Terminal
1DA-BD
1DA-BD
block
Terminal
block
*1 Shield
*2 Class-D
grounding
*2 Class-D
grounding
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition